Relay Contact Ratings: NEMA ICS5-2017

The “NEMA Standard ICS 5-2017” standard applies to general-purpose mechanical, electro-mechanical, and solid-state devices that are principally used in industrial applications for control-circuit switching and the control of solenoids rated not more than 600 volts.

Understanding Relay Contact Ratings

For purely resistive loads, calculating the required contact ampacity is a relatively simple application of Ohms Law. However, when the control circuit involves a solenoid (such as the coil and armature of a contactor), considerations of inrush current and inductive effects come into play.

Make Ratings

  • When a solenoid is first energized, it draws an inrush current that can be several times the steady-state current draw.
  • To account for this short duration surge in current the standard defines “make” values for when the contact closes and energizes a solenoid coil.
  • Make ratings may be larger than the continuous thermal rating because of the very short duration of a coil’s inrush current (typically 30ms or less).

Break Ratings

When a contact opens or “breaks” the circuit, it must be able to withstand the arcing that occurs as the contact faces separate. In DC circuits, arcing is exacerbated by the inductive effects of any contactor and relay coils in the circuit that are being de-energized when the contact opens.

Continuous Thermal Current

Mechanical contacts inherently introduce a small amount of resistance to the electrical circuits they are part of. Ohms Law tells us that this resistance generates heating effects that are proportional to the current flowing through the circuit. The tests prescribed in ICS 5-2017 stipulate the maximum allowable temperature rise for a given current flowing through the contacts.

Understanding Contact Rating Designations

Mechanical relay contact ratings are designated separately for AC circuits and DC circuits using a NUMBER/LETTER combination:

  • The letter designates maximum continuous current.
  • The number designates the maximum voltage rating.

This chart illustrates the key ratings of relay contacts under the standard. Since the voltage and current ratings are MAXIMUM values, the table lists VA (Volt-Ampere) values that are used to calculate the specific permissible current at any given voltage used in the relay’s application.

Applying the Relay Contact Ratings

Example 1:

A contact tested to A300 is used in a 277Vac application:

  • Letter Code A = 7200VA (make) & 720VA (break)
  • Maximum Continuous = 10A
  • Make = VA {make} / Voltage = 7200 / 277 = 25.9A
  • Break = VA {break} / Voltage = 720 / 277 = 2.59A

Example 2:

A contact tested to B150 is used in a 24Vac application.

  • Letter Code B = 3600VA (make) and 30VA (break)
  • Make = 3600 / 24 = 150A
  • Break = 360 / 24 = 15A
    • since the break rating cannot exceed the thermal rating, the maximum break rating is 5A

Example 3:

A contact tested to Q150 is used in a 125Vdc application.

  • Letter Code Q = 69VA (make & break)
  • Make and Break = 69 / 125 = 0.52A

Example 4:

A contact tested to N150 is used in a 24Vdc application.

  • Letter Code N = 275VA (make & break)
  • VA Calculation for make & break: 275 / 24 = 11.45A
  • Make = 11.45A
  • Break = 11.45A
    • since the break rating cannot exceed the maximum thermal value, the maximum break rating is 10A.

Stay Up to Date with NOARK Electric

To stay up to date with industry news, product releases, and free downloadable resources, subscribe to the NOARK Newsletter today.

TAGS:

Switchboards: Effective Electrical Power Distribution for Commercial and Industrial Facilities 

In the modern world, switchboards are the essential components at the heart of any electrical system, offering control, protection, and distribution of power. Learn more…

The Critical Importance of Surge Protective Devices (SPDs)

Low-voltage Surge Protective Devices (SPDs) play a critical role in safeguarding sensitive equipment from harmful electrical disturbances. Read more about NOARK’s U4 SPDs and their role…

NOARK Enclosed Breakers: Safety meets Innovation

NOARK’s enclosed breakers act like a robust fortress protecting electrical circuits from the chaos of overloads and short circuits.